Troubleshooting
Suction Pressure Transducer LEDs
“PRES 1-4” - There are LEDs for each of the Suction Pressure
Transducers. Since each compressor has a sensor, these LEDs which
are located on the top left of the WSHP-X Module will give a better
indication of which compressor is causing an alarm. See Table 10 for
PRES LED status descriptions. See Figure 11 for locations.
No. of
Blinks
Status
Solid On Sensor is Detected and is OK
Solid Off Sensor is Not Detected
1 Low Suction Pressure on this Compressor
2 Compressor is Locked Out
Table 10: PRES 1-4 LED Blink Codes
Figure 11: PRES 1-4 LED Locations
LED Diagnostics
“POWER” LED: When the WSHP-X Module is powered up, the
POWER LED (located above the address switches) should light up and
stay on continuously. If it does not light up, check to be sure that the
power wiring is connected to the board, the connections are tight, and
the VCM-X WSHP Series Controller or SA Series Controller is powered
(if connected). If after making all these checks, the POWER LED does
not light up, the module is probably defective.
“COMM” LED: When the WSHP-X Module is powered up while in
Stand Alone Mode, the COMM LED does not light up. When the module
is connected to the VCM-X WSHP Series Controller or SA Series Con-
troller, the COMM LED should light up, indicating Communications.
Each time Communications are detected, this LED should continuously
blink on and off for a half second. This LED should never stop checking
for a Communications signal. If it does not light up, check to be sure
that the power wiring is connected to the board, the connections are
tight, and the VCM-X WSHP Series Controller or SA Series Controller
is powered. If after making all these checks, the COMM LED does not
light up, the board is probably defective.
“STATUS” LED: As previously described, when the WSHP Module is
rst powered up, the STATUS LED will b
link out the Mode of Operation.
“ALARM” LED: As previously described, this LED will blink on and
off to indicate alarms and diagnostics.
NOTE: The WSHP-X Module contains no user-serviceable parts.
Contact quali ed technical personnel if your Module is
not operating correctly.