Orion-system Water Source Heat Pump X Module User Manual Page 23

  • Download
  • Add to my manuals
  • Print
  • Page
    / 32
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 22
Technical Guide
WSHP-X Module
23
System Status A Screens
Refer to the following map when navigating through the System Status
A Screens. From the SYSTEM STATUS A Screen, press
<ENTER> to
scroll through the screens.
SYSTEM
STATUS A
A1 COMP
OFF,PENDING,ON or
Reason for Fail
H2O TEMP
NO SENSR
Status Screens shown below will scroll automatically if LCD display is
left on this screen for 20 seconds.
SYSTEM A, COMPRESSOR 1
This screen displays the current status of the A1 Compressor.
OFF
PENDING: Compressor is off, but a request is made to be on, but the
1 minimum off time has not been met.
ON: HEAT or Cool
REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow
LEAVING WATER TEMPERATURE READING
OR “NO SENSOR”
A2 COMP
OFF,PENDING,ON or
Reason for Fail
SYSTEM A, COMPRESSOR 2
This screen displays the current status of the A2 Compressor.
OFF
PENDING: Compressor is off, but a request is made to be on, but the
1 minimum off time has not been met.
ON: HEAT or Cool
REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow
A1 PRES
XXX
SYSTEM A, COMPRESSOR 1 PRESSURE READING
A2 PRES
XXX or NOT USED
SYSTEM A, COMPRESSOR 2 PRESSURE READING
If Single Water Con guration, this screen will display “NOT USED.”
System Status A Screens
PO FLOW
YES or NO
PROOF OF WATER FLOW
AOUT1
X%
ANALOG OUTPUT 1 PERCENT
0 - 100%
AOUT2
X%
ANALOG OUTPUT 2 PERCENT
0 - 100%
Page view 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 31 32

Comments to this Manuals

No comments