Orion-system Water Source Heat Pump X Module User Manual Page 14

  • Download
  • Add to my manuals
  • Print
  • Page
    / 32
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 13
WSHP-X Module
Technical Guide
14
Installation and Wiring
VCM-X WSHP E-BUS or SA E-BUS
Controller to WSHP-X Module Wiring
for Dual Water Circuit
The WSHP-X Module connects to the E-BUS Controller using a modular
HSSC cable. The WSHP-X Module requires a 24 VAC power connection
with an appropriate VA rating. See Figure 8 below for wiring. (VCM-X
WSHP E-BUS Controller shown.)
Any E-BUS Module can be connected to the E-BUS Controllers E-BUS
port or can be daisy-chained together using HSSC cables.
NOTE: When using the WSHP-X Module, all compressors
will be wired from the WSHP-X Module, not the
VCM-X WSHP E-BUS Controller or SA E-BUS
Controller.
Figure 8: VCM-X E-BUS Controller to WSHP-X Module Wiring Diagram for Dual Water Circuit
Connect To Other
WattMaster-Approved
E-BUS Expansion Module(s)
WARNING!! Observe Polarity! All
boards must be wired with GND-to-
GND and 24 VAC-to-24 VAC.
Failure to observe polarity could
result in damage to the boards.
HSSC Cable
Connect To VCM-X E-BUS
Controller or SA E-BUS Controller
WATTMASTER CONTROLS
Y 102374 REV 0S
MADE IN USA
OE334-26-WSHPX-A Water Source
Heat Pump X Module
NOTE:
NORMALLY OPEN AND
RATED FOR 24 VAC POWER
ONLY
ALL RELAY OUTPUTS
ARE
COMP. A2 ENABLE
COMP. A1 ENABLE
R1
R4
R5
R3
R2
COMM
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
HVAC UNIT
CONNECTIONS
24 VAC Transformer
3 VA Minimum
Line Voltage
24 VAC
GND
WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and 24
VAC-to-24 VAC. Failure
to observe polarity could
result in damage to the
boards.
HSSC Cable
DIGITAL STG 1 (1.5-5V)
AO1
AO2
DIGITAL STG 2 (1.5-5V)
GND
T1
WATER POF A
BIN6
COM
E
LEAVING WATER TEMPERATURE
FOR SYSTEM B
LEAVING WATER TEMPERATURE
FOR SYSTEM A
T2
BIN7
WATER POF B
M
ENTER
UP
DOWN
ALARM
MENU
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
WattMaster Label
#SW000054
Rev.: 1A
E-BUS
CONNECT
E-BUS
CONNECT
+24 VAC
GND
www.orioncontrols.com
www.aaon.com
BIN 1
BIN 2
BIN 3
BIN 4
BIN 5
BIN 6
BIN 7
COM
- COMP. A1 EN.
- HEAT ENABLE
- COMP. A2 EN.
- WATER POF
- COMP. B1 EN.
- WATER POF
- COMP. B2 EN.
- COMMON
T1
T2
GND
- LEAVING WATER TEMP A
- GROUND
- LEAVING WATER TEMP B
AO1
A2O
STAGE 1- COMP. A1/B1-
STAGE 2 - COMP. A2/B2
DIGITAL COMP. A1, A2, B1, B2
RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC
COMP. A2 ENABLE
COMP. A1 ENABLE
R1
R2
R3
R4
R5
RC
RELAY COMMON
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
CONNECT TO CNTLR C2 TERM.
+5V
PRES
GND
+5V
PRES
GND
SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2
NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2
+5 NOT USED, PRES TO P6 & GND TO P5
+5 TO RED, PRES TO WHT & GND TO BLK
DIGITAL COMRESSORS
NON-DIGITAL COMPRESSORS
SIG 2
GND
+V
BK
RD
WH
SIG 1
GND
+V
BK
RD
WH
CIRCUIT A1
SUCTION PRESSURE
TRANSDUCER
SIG 2
GND
+V
BK
RD
WH
SIG 1
GND
+V
BK
RD
WH
CIRCUIT A2
SUCTION PRESSURE
TRANSDUCER
CIRCUIT B1
SUCTION PRESSURE
TRANSDUCER
CIRCUIT B2
SUCTION PRESSURE
TRANSDUCER
Page view 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 31 32

Comments to this Manuals

No comments