VCC-X Controller Technical Guide
APPENDIX D - VCC-X BACnet
®
107
VCC-X BACnet
®
Property Identi er:
BACNETPropertyIdenti er :
VcbxControlModeBits ::= ENUMERATED {
Supply Air Cooling Only (0),
Supply Air Tempering (1),
Outdoor Temperature Control (2),
Return Air Constant Volume Mode (3),
Space Temp Constant Volume Mode (4),
Space Temp w/ High OA Content (5),
Single Zone VAV (6)
}
VcbxControlStatusBits ::= ENUMERATED {
Unoccupied (0)
Occupied (1),
Override Mode (2),
Holiday Unoccupied (3),
Holiday Occupied (4),
Forced Occupied (5),
Forced Unoccupied (6),
Remote Contact Occupied (7)
}
VcbxHVACModeStatusBits ::= ENUMERATED {
Off (0),
Vent Mode (1),
Cooling Mode (2),
Heating Mode (3),
Vent RH Mode (4),
Cooling RH Mode (5),
Heating RH Mode (6),
Warm Up Mode (7),
Purge Mode (8),
Defrost Mode (9),
Cool Down Mode (10)
}
VcbxAlarmGroupBits ::= BIT STRING {
Sensor Alarm (0),
Mode of Operation Alarm (1),
Temperature Limit Alarm (2),
Expansion Module Alarm (3),
Compressor Module Alarm (4)
}
VCC-X BACnet
®
Parameters
Page view 106